Prepare PLC in TIA portal for external communication

How to configure Siemens S7 PLCs in TIA portal to communicate with SIA

Written by Mads Mikkelsen

Updated at August 25th, 2021

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Installation & Technical information
    Introduction SIA Connect Standalone SIA Connect ANY-Ware Cellular & WiFi connectivity
  • Configuration in the Web UI
    Getting started with the UI Connectors Instances Items Mapping Data System Network Tools & Add-ons DigiCert IoT Trust Manager
  • Connectors
    Siemens S7 Azure IoT Ethernet/IP Mitsubishi MELSEC OPC-UA Server SQL MQTT Omron Host Link REST API Omron FINS Keyence Beckhoff TwinCAT BACnet Virtual OPC-UA Client MS SQL File M-Bus Modbus
  • Scripting & Variables
    Data formatting
  • Developers
    API documentation Shadow API
  • Tutorials & Guides
    InfluxDB AWS IoT Core - Amazon Web Services Microsoft Power BI KaaIoT Siemens S7 AVEVA Insight SIA Connect Demo Rack Grafana Azure
  • General
+ More

Articles in this section:

  • Prepare PLC in TIA portal for external communication
  • Siemens S7 - Instance & item setup
  • Siemens S7 - Troubleshooting

In order for SIA to communicate with a Siemens S7 PLC you will need to grant it access to read and write from it.

This is done by enabling PUT/GET communication in the PLC. You will also have to grant access for read and/or write to the PLC depending.
To do this follow these steps:

  • Open the TIA project or go online on the PLC
  • Find the desired PLC in the TIA project. Click on its network properties
  • Go to Properties ➡ Protection
  • In the Protection view, select Full access if you need to both read and write to the PLC. 
  • In the Connection mechanism section mark the Permit access with PUT/GET communication from remote partner in order to allows SIA to R/W using PUT/GET commands.


Caution

Remember to unmark "Optimized block access" in the data blocks you want to R/W from as SIA does not support optimized access



Was this article helpful?