Ethernet/IP - Instance & item setup

How to setup a Ethernet/IP instance and item in SIA

Written by Mads Mikkelsen

Updated at June 30th, 2023

Contact Us

If you still have questions or prefer to get help directly from an agent, please submit a request.
We’ll get back to you as soon as possible.

Please fill out the contact form below and we will reply as soon as possible.

  • Installation & Technical information
    Introduction SIA Connect Standalone SIA Connect ANY-Ware Cellular & WiFi connectivity
  • Configuration in the Web UI
    Getting started with the UI Connectors Instances Items Mapping Data System Network Tools & Add-ons DigiCert IoT Trust Manager
  • Connectors
    Siemens S7 Azure IoT Ethernet/IP Mitsubishi MELSEC OPC-UA Server SQL MQTT Omron Host Link REST API Omron FINS Keyence Beckhoff TwinCAT BACnet Virtual OPC-UA Client MS SQL File M-Bus Modbus
  • Scripting & Variables
    Data formatting
  • Developers
    API documentation Shadow API
  • Tutorials & Guides
    InfluxDB AWS IoT Core - Amazon Web Services Microsoft Power BI KaaIoT Siemens S7 AVEVA Insight SIA Connect Demo Rack Grafana Azure
  • General
+ More

Articles in this section:

  • Ethernet/IP - Instance & item setup
  • Ethernet/IP - Troubleshooting

Table of Contents

ParametersInstanceItem Data typesAddress syntaxEthernet/IPPCCC

The Ethernet/IP connector connects SIA to Allen-Bradley and Omron controllers which are capable of communicating over Ethernet/IP or using PCCC with a gateway.


Parameters

When using the Ethernet/IP Connector both the instance and item have specific parameters. These parameters are required as they are needed to establish connection and to identify which addresses to read from.


Instance

The instance needs the following parameters to establish a connection to the PLC and devices:

Parameter Description
Address (instance default) The IP address of the Ethernet/IP controller.
Path The extended CIP path to where CPU controllers is placed. Used to navigate the Ethernet/IP traffic to the correct destination in the rack or hop to another network.

NOTE: Micro800 controllers does not require a path
NOTE: Required by ControlLogix and CompactLogix. Default: 1,0
NOTE: Required by Omron NJ/NX. Default: 18,IP-Address
Controller Type Select the variation of the Ethernet/IP controller. Select between the following controllers:
Allen-Bradley
  • Micro800
  • MicroLogix
  • CompactLogix
  • SLC500
  • PLC5
  • ControlLogix
  • FlexLogix

Omron

  • NJ/NX



Item

The item parameters that is needed to read the tags from the controller:

Parameter Description
Address Name or address of the tag in the controller.
Check address syntax for more information.
Type Data type used for determining the length of the tag in bytes and formatting it properly after a reading.
Check data types for more information on each data type.


Data types

The following table shows the different data types you can format the data as. 

Data type Return value
BOOL (bit) 0 or 1
Small integer -128 to 128
Unsigned small integer 0 to 255
Byte 0 to 255
Integer -32.767 to 32.767
Unsigned integer 0 to 65.535
Word 0 to 65.535
Double integer -2.147.483.647 to 2.147.483.647
Unsigned double integer 0 to 4.294.967.295
Double word 0 to 4.294.967.295
Real -3.4e38 to 3.4e38
String "Hello world!" (text inside tag)


Address syntax


Ethernet/IP

Controllers using Ethernet/IP can be accessed using naming syntax. 

Caution

Micro800 series requires the variables to be global in order to access them

Area Addressing Syntax
Global variable Bottle_Counter
Program variable Program:BottleManager.Bottle_Counter
Syntax: Program.<ProgramName>.VariableName
Array index Botte_Counter[4]
Syntax: VariableName[index]
Bit
Bottle_Counter.2
Program:BottleManager.Bottle_Counter.2
Program:BottleManager.Bottle_Counter[4].2



PCCC

The series from Allen-Bradley using PCCC such as PLC5, MicroLogix and SLCS500 can be addressed using Ethernet/IP. This though requires a bridge.

Caution

Accessing controllers running PCCC requires a converter bridge/gateway



Syntax
Format <Data Type><File>:<Element>
Format with bit <Data Type><File>:<Element>/<Bit>
<Data Type><File>:<Element>.<Bit>


Filetype Example
Bit B3:2/6
B3:2.6
Bit 6 in element 3
BCD D9:0
Float F8:0
Input I:20.2
I:20/2
Output O:10.2
O:10/2
Integer N7:0
N7:0/4
Bit 4 in element 0
Long Int L9:0
String ST9:0


allen-bradley omron eip ethernet/ip